How to Choose air cooled condensing units exporter?

Dec. 16, 2024
  • 3
  • 0
  • 0

How to Choose The Right Air-cooled Condenser

When selecting a refrigeration unit for a new installation, select the unit to provide the desired cooling effect to reduce and/or maintain the temperature of the product. This capacity is typically expressed in Btuh. Unit coolers (evaporators), compressors and metering devices are all selected based on the Btuh requirement of the refrigerant selected. The only major component not selected based on this Btuh requirement is the condenser.

Goto Kendall to know more.

 

The condenser must be selected for the total heat rejection (THR) of the system, which is the sum of the heat energy absorbed by the evaporator and the additional heat energy added to the refrigerant by the compressor. This additional heat energy is called the heat of compression. The heat of compression varies depending on the compressor design, so the compressor manufacturer's information should be used whenever possible. If this information is not available, many condenser manufacturers will provide a reference table to determine this value.


Manufactured from imported parts, our Two-Stage Air Cooled Piston Condensing Unit ensures maximum output and acquires less space to meet the latest standards. Having Bitzer's two-stage semi-hermetic compressor, our piston condensing unit is highly reliable and of good quality. With the advanced cooling mechanism, this condensing unit is the only choice of all clients in the world.

Air Cooled Piston Condensing Unit


We are feeling the pride to design quality accredited piston condensing units with top quality refrigeration parts. And we always manufacture and test parts of all Two-Stage Air Cooled Piston Condensing Units carefully to maintain OEM-QUALITY standards.

 

It is not always necessary to select an air-cooled condenser; many times, condensing units are selected for installation. Condensing units are selected based on the required Btuh capacity, and their condensers are selected by the condensing unit manufacturer. However, systems that use remote air-cooled condensers require a separate condenser selection.

 

To begin the selection process, first, determine the THR of the system by adding the heat of compression of the compressor (obtained from the compressor manufacturer's or condenser manufacturer's table.) If the condenser is installed above sea level, a correction factor needs to be applied to the THR. The condenser manufacturer will usually provide a table with the required correction factors.

 

Next, calculate the design temperature difference (TD), which is the design condensing temperature minus the design ambient temperature.

 

Design TD = condensing temperature - ambient temperature

 

Next, for the type of refrigerant in the system, use the condenser manufacturer's selection chart to choose a condenser based on THR and design temperature differences. Some manufacturers' charts may show the capacity of their condensers at a 1°F temperature differential. If necessary, you can determine the TD required at 1°F by dividing the THR by the design condenser TD as follows.

 

THR/°TD = THR ÷ calculated design condenser TD

 

If the required THR is between the two condenser capacities on the selection table, select the higher of the two. For example, you are selecting a remote air-cooled condenser for a system with a net cooling demand of 225,000 Btuh. The condenser will be installed at sea level, so there is no need for a height correction factor. It is a low-temperature system with an R-404A semi-hermetic suction cooling compressor with a design evaporative temperature of -20°F, an ambient outdoor temperature of 90°F, and a design condensing temperature of 110°F.

If you are looking for more details, kindly visit air cooled condensing units exporter.

 

Using this factor, the THR would be 348,750 Btuh (225,000 Btuh x 1.55). Design the condenser TD to be 20°F (110°F - 90°F).

 

Selecting the correct air-cooled condenser for the installation is an important part of ensuring the system operates properly and at maximum efficiency.


ABOUT US

Kendall is a professional manufacturer of refrigeration equipment that integrates research and development, design, production, and sales together. It is a high-tech enterprise specializing in intelligent energy-saving cold storage planning, design, and research; system integration and control; manufacturing, installation, and commissioning. At present, the company has obtained 25 national invention patents and 73 utility model patents. Let us help you find the best condenser for your project. When you contact us, please provide your detailed requirements. That will help us give you a valid quotation.

 

 


Choosing the Right Air-Cooled Condenser | -03-04

When choosing refrigeration equipment for a new installation, the equipment is selected to provide the required refrigeration effect to either reduce and/or maintain a product&#;s temperature. This capacity is normally stated in Btuh. The unit cooler (evaporator), compressor, and metering device are all selected based on this Btuh requirement for the selected refrigerant. The only major component not selected based on this Btuh requirement is the condenser.

A condenser must be selected for the system&#;s total of heat rejection (THR), which is the sum of the heat energy absorbed by the evaporator and the additional heat energy added to the refrigerant by the compressor. This additional heat energy is referred to as the heat of compression. The heat of compression varies with the compressor design, so the compressor manufacturer&#;s information should be used whenever possible. If this information is not available, many condenser manufacturers will provide a reference table to determine that value.

Selecting an air-cooled condenser is not always necessary; many times, a condensing unit is selected for the installation. The condensing unit is selected based on the required Btuh capacity and its condenser is selected by the condensing unit manufacturer. However, systems using a remote air-cooled condenser will need to have the condenser chosen separately.

To begin the selection process, first determine the system&#;s THR by adding in the compressor&#;s heat of compression (obtained from either the compressor manufacturer or a table from the condenser manufacturer). If the condenser will be installed above sea level, a correction factor will need to be applied to the THR. The condenser manufacturer will generally have a table available providing the required correction factors.

Next, calculate the design temperature difference (TD), which is the design condensing temperature minus the design ambient temperature:

Design TD = Condensing temperature - Ambient temperature

Next, for the system&#;s refrigerant type, use the condenser manufacturer&#;s selection chart to choose the condenser based on the THR and at the design temperature difference. Some manufacturers&#; charts may show their condenser&#;s capacity at a 1°F temperature difference. If necessary, you can determine the required TD at 1°F by dividing the THR by the design condenser TD:

THR/°TD = THR ÷ Calculated design condenser TD

If the required THR falls between two condenser capacities on the selection chart, chose the higher of the two. For example, you are selecting a remote air-cooled condenser for a system with a net refrigeration requirement of 225,000 Btuh. The condenser will be installed at sea level, so no factor for altitude correction is required. It is a low temperature system utilizing a R-404A semi-hermetic, suction cooled compressor with a design evaporating temperature of -20°F, an outdoor ambient of 90°F, and design condensing temperature of 110°F. According to the condenser manufacturer&#;s &#;Heat of Compression Factor for Suction Cooled Compressors&#; table, a multiplication factor of 1.55 should be used to determine the THR. Using this factor, the THR will be 348,750 Btuh (225,000 Btuh x 1.55). The design condenser TD will be 20°F (110°F - 90°F). Referencing the condenser manufacturer&#;s selection table for their R-404A condensers, it is possible to select the correct air-cooled condenser for the installation.

Selecting the correct air-cooled condenser for an installation is a vital part of ensuring the system operates properly and at peak efficiency.